Texas 250KVA Generator Set Cummins Engine

Texas 250KVA Generator Set Cummins Engine


Specifications
Details

TEXAS GENERATOR

Generator: 250KVA

Texas 250KVA Generator Set  Cummins Engine


 
SPECIFICATION
Voltage: 400v   Phase: 3  Standby power: 275kVA Prime power: 250kVA
Hz: 50Hz Current: 360A Power factor: 0.8
ALTERNATOR DATA
   Prime power 250KVA 200KW
   Frequency/speed 50HZ/1500rpm
   Exciter type Single bearing, Brushless, Self-excited
   Power factor 0.8
   Voltage adjust range                       ≥5% AVR
   Insulation Grade H
   Pole No 4
   Protection Grade IP23
   Phase / wire 3 phase 4 wires
ENGINE DATA
   Model Cummins 6LTAA8.9-G2
   No. Of Cylinder 6 Cylinders in Lines
   Cylinder Arrangement 4 Stroke
   Cycle Turbocharged and After Air cooled
   Aspiration direct Injection
   Bore×Stroke 114mm x145mm
   Displacement 8.9 L
   Prime Power/Speed 220KW @ 1500rpm
   Standby Power/Speed 240KW @ 1500rpm
   Speed Governor Electrical
   Cooling System Forced water cooling cycle
   Steady speed droop ≤1%
   Starter Moto DC24V
WEIGHT AND DIMENSION
   Size Genset Silent Type 3600*1400*1850mm
   Weight Genset Silent Type 2900 KG with 380L base fuel tank
FUEL SYSTEM
   Fuel Type Diesel
   Fuel Consumption at 100% Load 200gram/Kw.h
LUBE OIL SYSTEM
   Total lubrication system capacity 27.6 L
   Lube Oil Type CD15W Class and Above
COOLANT SYSTEM
   Total Coolant Capacity 49 L
   Max Water Temperature 104℃
   Thermostat 82-95℃
 